Start and Run Boost Settings
Appendix A
A-3
Procedure (cont.)
75%
Drive Output Current
25%
Drive Output Current
50%
Drive Output Current
100%
Drive Output Current
3
6V
2
0V
4
12V
5
18V
6
24V
7
30V
8
36V
9
42V
10
48V
Parameter 9 =
DC Boost =
3. Once smooth acceleration is obtained, set DC boost (Parameter 9) to 2,
then 3, 4, 5, 6, 7, 8, 9 and finally 10. Monitor and record drive output
current (Parameter 2) at each setting in the graph above. Compare the
values to those provided in the graph below.
If boost voltage is too low, the motor will be under excited and not be
able to develop full torque.
If boost voltage is too high, motor windings may saturate and cause
difficulty in starting.
The optimum setting for developing high motor torque is shown in
the graphs below.
75%
Drive Output Current
25%
Drive Output Current
50%
Drive Output Current
100%
Drive Output Current
3
6V
2
0V
4
12V
5
18V
6
24V
7
30V
8
36V
9
42V
10
48V
Parameter 9 =
DC Boost =
Typical Low HP Curve
1
1 Optimum Setting of Parameter 9
2 Optimum Setting of Parameter 48
3 Optimum Setting of Parameter 83
2
3
75%
Drive Output Current
25%
Drive Output Current
50%
Drive Output Current
100%
Drive Output Current
3
6V
2
0V
4
12V
5
18V
6
24V
7
30V
8
36V
9
42V
10
48V
Parameter 9 =
DC Boost =
Typical High HP Curve
1 Optimum Setting of Parameter 9
2 Optimum Setting of Parameter 48
3 Optimum Setting of Parameter 83
2
3
1