User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 129
Setpoint Programming and Operation Chapter 5
Setpoint Low Limit The value being used as a reference to
deactivate the setpoint for over comparisons,
or to activate the setpoint for under
comparisons.
0…10,000,000 Depends on type 0
Setpoint Action Delay The minimum time in seconds that the
setpoint limit must be exceeded continuously
before the setpoint will trigger.
0…3600 Sec (M4, M5) 0
0…30,000 0.1 Sec (M6, M8)
Setpoint Release
Delay
The minimum time in seconds that the
setpoint limit must not be exceeded
continuously before the setpoint releases.
0…3600 Sec (M4, M5) 0
0…30,000 0.1 Sec (M6, M8)
Setpoint Action Type The action that occurs when the setpoint is
triggered.
0…32 (see details in the
Setpoint Action Type table on
page 131
)
0
Clear Accumulated
Time
Clear the time accumulator for this setpoint Yes
No
N/A
Setpoint Configuration
Parameter Name Parameter Description Range Units Default
Setpoint Types
Setpoint Type Description Units M4,
M5
M6 M8
0 Not used - •••
1
Voltage
(1)
Volts •••
2
Current
(1)
Amps •••
3 Voltage unbalance Percent •••
4 Current unbalance •••
5 Neutral current Amps •••
6 W Watts •••
7VAR VARs•••
8VA VA•••
9 Total true PF Percent •••
10 Total disp PF •••
11 Total dist PF •••
12 W demand Watts •••
13 VAR demand VARs •••
14 VA demand VA •••
15 Amp demand Amps •••
16 Projected amp demand Amps •••
17 Projected W Demand Watts •••
18 Projected VAR Demand VARs •••
19 Projected VA Demand VA •••
20 Frequency Hz •••
21 Phase rotation - •••
22 Crest factor voltage Volts •••
23 Crest factor current Amps •••