User Manual, Firmware rev. 3.0 or LATER Owner's manual

146 Publication 1404-UM001F-EN-P - November 2009
Chapter 7 Data Logging
Configuring the Event Log by Using Communication
You may configure the Event Log by performing a valid table write to
the Event Log Configuration/Read-back Record Select
table. This
read/write data table contains these six integer elements:
Password: A valid password is required to set configuration
options or -1 to select a record for read-back
DeviceNet unique write identifier
Read-back mode: see below
Status input logging: 0 disables; 1 enables
Number of events logged: this read-only element is ignored on a
write
Time/date set logging: 0 disables; 1 enables
Status Error Codes
Bits Hex Description
bit 0 0001h Master module code flash status
bit 1 0002h Master module data flash status
bit 2 0004h Master module RAM Status
bit 3 0008h Reserved for factory use
bit 4 0010h Master module NVRAM status
bit 5 0020h Master module data acquisition status
bit 6 0040h Master module real time clock status
bit 7 0080h Reserved for factory use
bit 8 0100h Reserved for factory use
bit 9 0200h Display module status
bit 10 0400h Master module watchdog timer status
bit 11 0800h Master module optional communication status
bit 12
15
1000h
-8000h
Reserved for factory use