Chapter 7 Data Logging
• Mid peak PM – selects afternoon mid peak time-of-use hours.
Default 120 (78 Hex, 3:00…6:59 p.m.)
• Peak AM – selects morning peak time-of-use hours. Default 2048
(800 Hex, 11:00…11:59 a.m.)
• Peak PM – selects afternoon peak time-of-use hours. Default 7 (7
Hex, 12:00 noon…2:59 p.m.)
Reading Time-of-use Log Data
The power monitor stores the TOU log in three sets of 13 records
each, one set for real energy and demand, a second for reactive
energy and demand, and the last for apparent energy and demand.
For each set, record 0 contains the in-process records for the current
month. Records are stored to non-volatile memory every 2 minutes.
Records 1…12 contain the monthly records for the previous 12
months. When the log day occurs, the records are shifted down, with
the record 0 moving into record 1 and the oldest record being deleted.
The Time of Use Records – Real Energy and Demand
table contains
the real energy and demand time-of-use data from the record selected
during the most recent write to the Time of Use Register Configuration
table. This read-only table of 12 floating-point elements contains the
following data:
• Off-peak MWh
• Off-peak kWh
• Off-peak demand Watts
• Mid-peak MWh
• Mid-peak kWh
• Mid-peak demand Watts
• Peak MWh
• Peak kWh
• Peak demand Watts
• Start date in YY/MM/DD format
• End date in YY/MM/DD format
• Record number 0…12
The Time of Use Records – Reactive Energy and Demand
and Time of
Use Records – Apparent Energy and Demand tables are identical
except that one contains reactive energy and demand TOU data and
the other contains apparent energy and demand TOU data.