User Manual, Firmware rev. 3.0 or LATER Owner's manual
188 Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Summary of Powermonitor 3000 Data Tables for all Communication Options
Data Table Name and Description
(1)
Data
Access
Indexed
Reads
(3)
File No.
(4)
(DF1, CSP)
Remote I/O
BT Size
Assy
Instance
(CIP, DNet)
Modbus
Starting
Address
(6)
No. of
Elements
Applies to
Configur-
able
Refer to
Page
M4, M5
M6
M8
Remote I/O, DeviceNet, EtherNet/IP and
ControlNet I/O Messaging Parameters
R/W - - I/O 1,2
-
-
(7)
•••
•
(7)
191
Discrete Data Parameters R N9 10 3 30001 6 ••• 193
Basic Device Configuration Parameters R/W F10 20 4,5 40001
8 or 9
(8)
••• 194
Date and Time Parameters R/W N11 12 6,7 40101 8 ••• 195
Advanced Device Configuration Parameters R/W N12 26 8,9 40201 26 ••• 196
Native Communication Configuration Parameters R/W N13 11 10,11 40301
10
(9)
••• 198
Optional Communication Configuration Parameters R/W N14 24 12,13 40401 20 ••• 199
Metering Voltage, Current, and Frequency Result
Parameters
R F15 38 14 30101 14 ••• 205
Metering Sequence Voltage, and Current Results
Parameters
R F16 27 15 30201 11 ••• 206
Metering Power Results Parameters R F17 31 16 30301 13 ••• 207
Metering Demand Results Parameters R F18 25 17 30401 10 ••• 208
Metering Power Factor Results Parameters R F19 33 18 30501 13 ••• 209
Metering Real and Apparent Energy Results
Parameters
R/W N20 29 19,20 40501 23 ••• 210
Metering Reactive Energy and Amp-hour Results
Parameters
R/W N21 30 21,22 40601 23 ••• 211
Selftest/Diagnostic Results Parameters R N22 36 23 30601 27 ••• 212
DF1 PCCC Diagnostic Status Reply Parameters R
(5)
-- - - ••• 213
Setpoint Setup/Read-back Select and Status
Parameters
R/W • N23 22 24,25 40701 16 ••• 215
Trend Log Configuration/Read-back Record Select
Parameters
R/W N24 34 26,27 40801 26 ••• 220
Trend Log Results Parameters R • F25 48 28 30701
14 or 22
(10)
••• • 221
Min/Max Log Configuration/Read-back Select
Parameters
R/W N26 13 29,30 40901 9 ••• 223
Min/Max Log Results Parameters R • F27 28 31 30801 11 ••• 227
Event Log Configuration/Read-back Record Select
Parameters
R/W N28 9 32,33 41001 6 ••• 228
Event Log Results Parameters R • N29 21 34 30901 14,17,18
(11)
••• 229
User-configured Table Setup Parameters R/W N30 35 35,36 41101 26 ••• 233
User-configured Table Results Parameters R F31 62 37 31001
14 or 23
(12)
••• • 235
Write Error Status Parameters R N32 4 38 31101 2 ••• 236
Harmonic Analysis Configuration/Read-back Select
Parameters
R/W N33 14 39,40 41201 9 ••• 237
Harmonic Results; THD, Crest Factor, and More
Parameters
R • F34 23 41 31201
9 or 10
(13)
••• 238
Harmonic Results; Odd Harmonics 1…21
Parameters
R • F35 39 42 - 14 •• 239
Harmonic Results; Odd Harmonics 23…41
Parameters
R • F36 40 43 - 14 •• 240
Harmonic Results; Even Harmonics 2…20
Parameters
R • F37 41 44 - 14 •• 241
Harmonic Results; Even Harmonics 22…40
Parameters
R • F38 42 45 - 14 •• 242
Oscillograph Configuration/Read-back Data Select
Parameters
R/W N39 15 46,47 - 11 •• 243