Publication 1404-UM001F-EN-P - November 2009 197
Powermonitor 3000 Data Tables Appendix A
14 40215 Restore factory default
config
0…1 - 0 0 = No action 1 = Restore factory default settings
15 40216 Clear status input counters 0…3 - 0 0 = No action
1 = Clear counter #1
2 = Clear counter #2
3 = Clear both
16 40217 Wdog action 0…1 - 1 0 = Restart, log an event and halt operation
1 = Restart, log an event and resume
Refer to
Watchdog Timeout Action on page 55
17 40218 Force relay output 0…3 - 0 0 = No change
1 = Force energize the relay
2 = Force de-energize the relay
3 = Release force of relay output
Overrides setpoint or pulse output control
18 40219 Force solid-state KYZ output 0…3 - 0
19 40220 Default relay state in event
of communication loss
0…3 - 0 0 = Last state / resume
1 = Last state / freeze
2 = De-energize / resume
3 = De-energize / freeze
Refer to
Communication Loss Behavior on
page 140
20 40221 Default KYZ state in event
of communication loss
21 40222 DM text scroll rate 0…1 - 1 0 = Slow; 1 = Fast
22 40223 Energy counter rollover 4…15 Digits 15 Refer to
Configurable Energy Counter Rollover
on page 35
23 40224 Forced demand sync delay 0…900 s 10 0 = Disable, 1…900 = number of seconds delay
24 40225 Reserved 0 - 0 Reserved. Must be 0 on a write, returns 0
25 40226 Reserved 0 - 0 Reserved. Must be 0 on a write, returns 0
Advanced Device Configuration
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment