User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 201
Powermonitor 3000 Data Tables Appendix A
Remote I/O
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 40401 Password 0…9999 0 Valid password required to change configuration data. Returns -1
1 40402 Logical rack address 1…63 1 The scanner uses rack address 0
2 40403 Module group 0,2,4,6 0 0 = Group 0 (acts like the first 2 rack slots)
2 = Group 2
4 = Group 4
6 = Group 6
3 40404 Last rack 0…1 0 0 = No
1 = Yes
4 40405 Baud rate 0…2 0 0 = 57.6 Kbps
1 = 115.2 Kbps
2 = 230.4 Kbps
5 40406 Reserved 0 0 Reserved. Must be 0 on a write, returns 0
6 40407
7 40408
8 40409
9 40410
10 40411
11 40412
12 40413
13 40414
14 40415
15 40416
16 40417
17 40418
18 40419
19 40420