User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 205
Powermonitor 3000 Data Tables Appendix A
Metering Voltage, Current, and Frequency Result Parameters
CSP File No. F15
Remote I/O BT 38
CIP Assy. Inst. 14
No. of Elements 14
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Metering Voltage, Current, and Frequency Result
Element
No.
Modbus
Address
Element name Units Range Comment
0 30101-2 L1 Current Amps (A)
0.0…999.9x10
21
Refer to Voltage, Current, and Frequency Results on
page 30.
1 30103-4 L2 Current
0.0…999.9x10
21
2 30105-6 L3 Current
0.0…999.9x10
21
3 30107-8 Avg. Current
0.0…999.9x10
21
4 30109-10 L1-N Voltage Volts (V)
0.0…999.9x10
21
5 30111-12 L2-N Voltage
0.0…999.9x10
21
6 30113-14 L3-N Voltage
0.0…999.9x10
21
7 30115-16 Avg. L-N Voltage
0.0…999.9x10
21
8 30117-18 L1-L2 Voltage
0.0 …999.9x10
21
9 30119-20 L2-L3 Voltage
0.0 …999.9x10
21
10 30121-22 L3-L1 Voltage
0.0…999.9x10
21
11 30123-24 Avg L-L Voltage
0.0…999.9x10
21
12 30125-26 Frequency, last cycle Hertz (Hz) 40.0…75.0 Returns 0 or 999.0 if out of range.
13 30127-28 Metering iteration - 0…32,767 Increments by 1…32,767, rolls over to 0.