Appendix A Powermonitor 3000 Data Tables
Metering Sequence Voltage, and Current Results Parameters
CSP File No. F16
Remote I/O BT 27
CIP Assy. Inst. 15
No. of Elements 11
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Metering Sequence Voltage, and Current Results
Element
No.
Modbus
Address
Element name Units Range Comment
0 30201-02 L4 (Zero sequence) Current Amps (A)
0.0…999.9x10
21
Refer to Symmetrical Component Analysis
Results on page 31.
1 30203-04 Positive Sequence Current
0.0…999.9x10
21
2 30205-06 Negative Sequence Current
0.0…999.9x10
21
3 30207-08 % Current unbalance Per Cent 0.0…100.0
4 30209-10 Positive Sequence Voltage Volts (V)
0.0…999.9x10
21
5 30211-12 Negative Sequence Voltage
0.0…999.9x10
21
6 30213-14 % Voltage unbalance Per Cent 0.0…100.0
7 30215-16 Phase rotation - 0…2 0 = No rotation.
1 = ABC rotation.
2 = ACB rotation.
8 30217-18 Average frequency Hertz (Hz) 40.0…75.0 Average of the last 1 or 8 cycles.
Returns 0 or 999.0 if out of range.
9 30219-20 Frequency source - 0… 2 0 = V1, 1 = V2, 2 = V3.
10 30221-22 Metering iteration - 0…32,767 Increments by 1…32,767, rolls over to 0.