User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 211
Powermonitor 3000 Data Tables Appendix A
Metering Reactive Energy and Amp-hour Results Parameters
CSP File No. N21
Remote I/O BT 30
CIP Assy. Inst. 21 (Write), 22 (Read)
No. of Elements 23
User Configurable No
Data Type Integer
Data Access Read/Write
PM3000 Type All
Metering Reactive Energy and Amp-hour Results
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40601 Password 0…9999 - 0 Required to clear or preset energy counters.
Returns -1.
1 40602 Parameter select 0…7 - Refer to
How to Clear or Preset Energy
Counters by Using Communication on
page 120.
2 40603
kVARh forward ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999 kVARh
3 40604
4 40605
5 40606
6 40607
7 40608
kVARh reverse ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999
8 40609
9 40610
10 40611
11 40612
12 40613
kVARh net ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999
13 40614
14 40615
15 40616
16 40617
17 40618
kAh ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999 kAh
18 40619
19 40620
20 40621
21 40622
22 40623 Metering iteration 0…32,767 - Increments by 1…32,767, rolls over to 0.