User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 213
Powermonitor 3000 Data Tables Appendix A
14 30615 ASIC build # 0…9999 Revision number of the code that was used to fabricate the
ASIC.
15 30616 Option communication FRN 0…9999 100 indicates version 1.00, 103 indicates version 1.03… 0 =
none (catalog numbers ending in -000, -232)
16 30617 Display module FRN 0…9999 104 indicates version 1.04, 105 indicates version 1.05…
Returns 0 if no DM connected
17 30618 Reserved 0 Returns 0
18 30619 Digital board revision 0…7 0 = 02A, 1 = 03A…
19 30620 Analog board revision 0…7 0 = 02A, 1 = 03A…
20 30621 Reserved 0 Returns 0
21 30622 Reserved 0 Returns 0
22 30623 MM Device ID 0…255 Sequentially assigned at time of manufacture. May not be
changed.
23 30624 Master module type, current 4,5,6,or 8 4 = M4, 5 = M5, 6 = M6, 8 = M8; reflects any upgrades
24 30625 Display module type 0…1 0 = No display module connected
1 = 1404-DM connected to master module
25 30626 Option communication type - 00 = No optional communication (native RS-485 only)
81 = DeviceNet version 1
82 = ControlNet
84 = Remote I/O
86 = RS-232
88 = DeviceNet version 2
89 = IEC870 comm card
26 30627 Accuracy Class 0…2 Indicates revenue metering accuracy class as manufactured
(refer to page 29
).
0 = Class 1
1 = Class 0.5
2 = Class 0.2
Selftest/Diagnostic Results
Element
No.
Modbus
Address
Element name Range Comment
TIP
This is not truly a data table, but a reply to a PCCC diagnostic status
request (used by RSWho to display text and an icon for the
Powermonitor 3000 unit). This data is not accessible using Modbus.
DF1 PCCC Diagnostic Status Reply Parameters
Byte Bits Contents Description
1 0…1 Mode/status Unused
2…3
4…7
2 0…7 Type extender EE
3 0…7 Extended interface type 36h = DF1 half-duplex slave (via native RS485 port or RS-232 port)
65h = Ethernet
4 0…7 Extended processor type 8Ah; 1404 Powermonitor 3000 products