User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 223
Powermonitor 3000 Data Tables Appendix A
Min/Max Log Configuration/Read-back Select Parameters
CSP File No. N26
Remote I/O BT 13
CIP Assy. Inst. 29 (Write), 30 (Read)
No. of Elements 9
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Min/Max Log Configuration/Read-back Select
Element
No.
Modbus
Address
Element Name Range Default
Value
Comment
0 40901 Password 0…9999 0 Required for configuration, -1 for readback
select, returns -1.
1 40902 Min/max parameter to read 0…73 1 Refer to
Interfacing with the Min/Max Log
by Using Communication on page 154.
2 40903 Read-back mode 0…1 0
3 40904 Enable/disable Min/max log 0…1 1
4 40905 Clear min/max log 0…1 0
5 40906 Timestamp of last min/max clear; year
month/day
hour/minute
second/hsec
1998…2097 -
6 40907 0101…1231 -
7 40908 0000…2359 -
8 40909 0000…5999 -