User Manual, Firmware rev. 3.0 or LATER Owner's manual
228 Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Event Log Configuration/Read-back Record Select Parameters
CSP File No. N28
Remote I/O BT 9
CIP Assy. Inst. 32 (Write), 33 (Read)
No. of Elements 6
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Applies to: Event Log Results Parameters on page 229
Event Log Configuration/Read-back Record Select
Element
No.
Modbus
Address
Element Name Range Default
Value
Comment
0 41001 Password 0…9999 0 Required for configuration, -1 for readback
select, returns -1
1 41002 DeviceNet unique write identifier -32,768…32,767 0 Refer to
DeviceNet Unique Write Identifier on
page 103
2 41003 Read-back mode 0…6 2 Refer to Configuring the Event Log by Using
Communication on page 146
3 41004 Enable/disable logging status
input changes
0…1 0
4 41005 # events in the event log 1…50 (M4,M5)
1…100 (M6, M8)
-
5 41006 Enable/disable logging of
time/date set
0…1 1