User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 229
Powermonitor 3000 Data Tables Appendix A
Event Log Results Parameters
CSP File No. N29
Remote I/O BT 21
CIP Assy. Inst. 34
No. of Elements 14, 17, or 18 (see table)
User Configurable No
Data Type Integer
Data Access Read only
PM3000 Type See table
Event Log Results
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element Name Range Comment
0 30901 •••Reserved 0 Returns 0
1 30902 •••Internal identifier 0 …32768 Refer to
Reading Data from the Event Log
by Using Communication on page 147
2 30903 •••Timestamp of event; Year
Month/day
Hour/minute
Second/hsec
1998…2097 Refer to
Expressing Data in Data Tables on
page 82
3 30904 ••• 0101…1231
4 30905 ••• 0000…2359
5 30906 ••• 0000…5999
6 30907 •••Event type 0…19 Refer to
List of Event Types Parameters
7 30908 •••Event code - Refer to Reading Data from the Event Log
by Using Communication on page 147
8 30909 •••Setpoint type 0…52
9 30910 •••Setpoint evaluation condition 0…5
10 30911 •••Setpoint level integer
exponent
0…9999
11 30912 ••• -21…21
12 30913 •••Setpoint action/release delay 0…3600 (M4, M5)
0…30,000 (M6, M8)
13 30914 •••Setpoint action 0…32 (M4, M5)
0…43 (M6, M8)
14 30915 ••Sustain limit timer integer
exponent
0…9999
15 30916 •• -4…21
16 30917 ••Capture identifier 0…999
17 30918 • Reserved 0 Returns 0