User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 231
Powermonitor 3000 Data Tables Appendix A
List of Event Types Parameters
Applies to Event Log Results Parameters on page 229
PM3000 Type See table
List of Event Types
Event
Code.
M4
M5
M
6
M
8
Event Type Event Command
Code
Comment
0 ••No event 0 The log starts with no events recorded
1 ••Setpoint triggered Setpoint Number A setpoint activated
2 ••Setpoint released A previously active setpoint released
3 ••Relay force energized Relay Number 1 = Form C relay, 2 = KYZ
4 ••Relay force de-energized
5 ••Relay force released
6 ••Status input set Status Input Number
7 ••Status input cleared
8 ••kWh counter set or cleared 1 Records command action
8 ••kVARh counter set or cleared 2
8 ••kVAh counter set or cleared 3
8 ••Ah counter set or cleared 4
8 ••All energy counters cleared 5
8 ••Trend log cleared 6
8 ••Min/max log cleared 7
8 ••Factory defaults restored 8
8 ••Status input #1 counter cleared 9
8 ••Status input #2 counter cleared 10
8 ••Reserved 11
8 ••Single setpoint timer cleared 12
8 ••All setpoint timers cleared 13
9 ••Power-up 0 Control power was applied
10 ••Power-down 0 Control power was lost or internal reset occurred
11 ••Selftest failure Status Error Code Refer to
Status Error Codes (bitfield)
12 ••Date/time set 0 The date and/or time was set or altered
13 ••Change of non-setpoint config data 0
14 ••Change of setpoint config data 0
15 ••NVRAM Clr 0 NVRAM has been cleared due to an extended loss
of control power or internal error
16 Transient detected