User Manual, Firmware rev. 3.0 or LATER Owner's manual
236 Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Write Error Status Parameters
CSP File No. N32
Remote I/O BT 4
CIP Assy. Inst. 38
No. of Elements 2
User Configurable No
Data Type Integer
Data Access Read only
PM3000 Type All
Write Error Status
Element
No.
Modbus
Address
Element Name Range Default
Value
Comment
0 31101 File, instance or BT
number
-
-
Identifies data table written to last, value depends on comms
type. For Modbus, starting address of table written to last.
1 31102 Offending Element -1 = Last write was successful
0…26 = first unacceptable element of unsuccessful write
For Remote I/O Only:
0 = Last write was successful
1…27 = First unacceptable word of unsuccessful write
For Modbus Only:
-1 = Last write was successful
40,001…42,001 - first unacceptable address of unsuccessful
write.