User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 251
Powermonitor 3000 Data Tables Appendix A
Transient Capture Clear/Read-back Data Select Parameters
CSP File No. N45
Remote I/O BT 17
CIP Assy. Inst. 55 (Write), 56 (Read)
No. of Elements 13
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type M8 only
Applies to Transient Capture Results Parameters on page 252
Transient Capture Clear/Read-back Data Select
Element
No.
Modbus
Address
Element Name Range Default
Value
Comment
0 - Password 0…9999 0 Required for configuration, -1 for readback select, returns
-1.
1 - Dnet unique write
identifier
-32,768…32,767 0 Refer to
DeviceNet Unique Write Identifier on page 103.
2 - Capture number 0…6 1 Refer to
Reading Transient Capture Data on page 182.
3 - Channel number 1…7 1
4 - Block number See page 90 1
5 - Read-back mode 0…2 0
6 - Clear command 0…3 0
7- Reserved 0 0
8- Reserved 0 0
9- Reserved 0 0
10 - Capture clear status 0…63 -
11 - Capture ready status 0…63 -
12 - Reserved 0 0