Appendix A Powermonitor 3000 Data Tables
Time of Use Records – Reactive Energy and Demand Parameters
CSP File No. F57
Remote I/O BT 52
CIP Assy. Inst. 73
No. of Elements 12
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Time of Use Records – Reactive Energy and Demand
Element
No.
Modbus
Address
Element Name Range Units Comment
0 32501-02 Off-peak reactive
energy
-999,999.0…
999,999.0
MVARh Refer to
Reading Time-of-use Log Data on
page 158
1 32503-04 Off-peak reactive
energy
-999.999.999…
999.999.999
kVARh
2 32505-06 Off-peak demand
VARs
0.0…999.9 x 10
21
VAR
3 32507-08 Mid-peak reactive
energy
-999,999.0…
999,999.0
MVARh
4 32509-10 Mid-peak reactive
energy
-999.999.999…
999.999.999
kVARh
5 32511-12 Mid-peak demand
VARs
0.0…999.9 x 10
21
VAR
6 32513-14 Peak reactive energy -999,999.0…
999,999.0
MVARh
7 32515-16 Peak reactive energy -999.999.999…
999.999.999
kVARh
8 32517-18 Peak demand VARs
0.0…999.9 x 10
21
VAR
9 32519-20 Record number 0…12
10 32521-22 Start date 000101…991231 YYMMDD Start month / day for data stored in this
record, inclusive
11 33523-24 End date 000101…991231 YYMMDD End month / day for data stored in this
record, inclusive