User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 265
Powermonitor 3000 Data Tables Appendix A
Time of Use Records – Apparent Energy and Demand Parameters
CSP File No. F58
Remote I/O BT 53
CIP Assy. Inst. 74
No. of Elements 12
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Time of Use Records – Apparent Energy and Demand
Element
No.
Modbus
Address
Element Name Range Units Comment
0 32601-02 Off-peak apparent
energy
-999,999.0…
999,999.0
MVAh Refer to
Reading Time-of-use Log Data on
page 158
1 32603-04 Off-peak apparent
energy
-999.999.999…
999.999.999
kVAh
2 32605-06 Off-peak demand VA
0.0…999.9 x 10
21
VA
3 32607-08 Mid-peak apparent
energy
-999,999.0…
999,999.0
MVAh
4 32609-10 Mid-peak apparent
energy
-999.999.999…
999.999.999
kVAh
5 32611-12 Mid-peak demand VA
0.0…999.9 x 10
21
VA
6 32613-14 Peak apparent energy -999,999.0…
999,999.0
MVAh
7 32615-16 Peak apparent energy -999.999.999…
999.999.999
kVAh
8 32617-18 Peak demand VA
0.0…999.9 x 10
21
VA
9 32619-20 Record number 0…12
10 32621-22 Start date 000101…991231 YYMMDD Start month / day for data stored in this
record, inclusive
11 33623-24 End date 000101…991231 YYMMDD End month / day for data stored in this
record, inclusive