User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 315
Sample Applications Appendix C
You must enter data into the Default and Custom tags.
Refer to
User-configured Data Table on page 121 for the structure and
rules for the User-configured Table Setup
data table and its default
settings.
See
Parameters for Trend Log and Configurable Table Parameters on
page 268 for parameters that may be included in the User Configured
Table Setup.
ControlLogix Tags Used
Tag Name Type # of
Elems
Description Table #
msgReadOld MESSAGE N/A Read Existing Config N30
msgWriteNew MESSAGE N/A Write New Config. N30
msgGetStatus MESSAGE N/A Write Status N32
Start BOOL 1 Start Operation
Failed BOOL 1 Failure Flag
Success BOOL 1 Success Flag
Oneshot_1 BOOL 1 One shot
Oneshot_2 BOOL 1 One shot
Timer1 TIMER 1 Inter-message Delay
Timer2 TIMER 1 PM3000 Reset Time
Counter1 COUNTER 1 Message Retry
Default INT 26 Default Configuration
Custom INT 26 Custom Configuration
Old INT 26 Previous Config
Download INT 26 New Config to Write
Pwd INT 1 PM3000 Password
Status INT 2 Write Status
Select INT 1 User Selection
IMPORTANT
Words 0…3 of the User Configurable Table Setup array must have
specific values.
Word 0: power monitor password (default = 0)
Word 1 must be one of the following decimal values:
31, for CSP/PCCC
1 or 37 for CIP
Word 2: zero (0) for writes to table 31. For configuring instance 1:
0 = all integer or data type, 1 = float data type.
Word 3: between 1 and 295 incl.