User Manual, Firmware rev. 3.0 or LATER Owner's manual

Publication 1404-UM001F-EN-P - November 2009 325
Sample Applications Appendix C
0002
N9:11
0
Allow Write
EQU
Equal
Source A N9:6
8<
Source B 4
4<
EQU
EQU
Equal
Source A N9:6
8<
Source B 52
52<
EQU
JSR
Jump To Subroutine
SBR File Number U:4
JSR
When a write of a float file is being performed it is necessary to swap the words in teh float file before sending the write request.
This is only necessary for Instance 4 or Instance 52.
0003
N9:11
0
Allow Write
B3:0
0
Message Pending
FLL
Fill File
Source 0
Dest #N7:0
Length 65
FLL
COP
Copy File
Source #N9:0
Dest #N7:0
Length 10
COP
COP
Copy File
Source #N14:0
Dest #N7:10
Length 64
COP
COP
Copy File
Source #N7:10
Dest #M0:3.1100
Length 65
COP
L
N7:0
15
Enable Transfer Bit
COP
Copy File
Source #N7:0
Dest #M0:3.1000
Length 10
COP
L
B3:0
0
Message Pending
Allow the scanner to write to the power monitor. Put the new integer configuration data in N14 starting at location 0. Put the configuration
if it is of float type in file F13 starting with word 0. Enter the rest of the CIP message information needed for transfer in N9 starting with
word 0. The process is similar to the request of information except that the size in words of the data to write is to appear in N7:9 and the
service to be performed is changed.