Rockwell Automation Publication 1407-UM001G-EN-P - April 2013 133
CGCM Unit Software Interface Chapter 6
7 1 Bool 0 BusV_Present Bus Voltage Present - 0=False, 1=True
Bool 1 GenV_Present Generator Voltage Present
Bool 2 PhRotMatch Phase Rotation Match
Bool 3 V_Match Voltage Match
Bool 4 FreqMatch Frequency Match
Bool 5 PhMatch Phase Match
Bool 6 CGCMInControl CGCM Control 0=No, 1=Yes
Bool 7 Spare1 CGCM is active in a redundant pair 0=False, 1=True
8 1 Bool 0 Activebus_A_B Bus A/B Active - 0=Bus A,
1=Bus B
Bool 1 Raise_V Raise Voltage 0=False, 1=True
Bool 2 Lower_V Lower Voltage
Bool 3 Raise_Freq Raise Frequency
Bool 4 Lower_Freq Lower Frequency
Bool 5 Raise_Ph Raise Phase
Bool 6 Lower_Ph Lower Phase
Bool 7 SyncFailure Synchronization Failure
9 1 Bool 0 AutoSync Auto Synchronization Enabled - 0=Disabled,
1=Enabled
Bool 1 CheckSync Check Synchronization Enabled
Bool 2 PermissiveSync Permissive Synchronization
Enabled
Bool 3 UndefinedSyncMode Undefined Synchronization Mode 0=No, 1=Yes
Bool 4 SyncModeConflict Synchronization Mode Conflict
Bool 5 SyncDeadBus Dead Bus Synchronization
Bool 6 CloseBusA_Brkr Close Bus A Breaker 0=Don’t Close,
1=Close
Bool 7 CloseBusB_Brkr Close Bus B Breaker
10 1 Bool 0 Spare2 Indicates when the excitation
output short circuit protection is
active.
- 0 = Inactive
1 = Active
Bool 1 FreqLessThan10Hz Frequency Less Than 10 Hz 0=False, 1=True
Bool 2 Spare3
Bool 3 SetptTraverseActive Traverse Setpoint Active 0=Setpoint,
1=Traverse
Bool 4 ShortedRotDiodeFlt Rotating Diode Shorted Fault 0=Inactive,
1=Active
Bool 5 OpenRotDiodeFlt Rotating Diode Open Fault
Bool 6 HardwareExcEned Hardware Excitation Enabled 0=Disabled,
1=Enabled
Bool 7 SoftwareExcEned Software Excitation Enabled
Table 7 - Scheduled Read Data Table
Byte Size in
Bytes
Type Bits Tag Name Description-+ Units Range