Manual
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013 137
CGCM Unit Software Interface Chapter 6
3 1 Bool 0 AutoSyncEn Auto Synchronization Enable - 0=Disabled,
1=Enabled
Bool 1 CheckSyncEn Check Synchronization Enable
Bool 2 PermissiveSyncEn Permissive Synchronization
Enable
Bool 3 Spare5
Bool 4 Spare6
Bool 5 Bus A_B_Select Bus A/B Select 0=Bus A, 1=Bus B
Bool 6 DeadBusClosureEn Dead Bus Closure Enable 0=Disabled,
1=Enabled
Bool 7 InitiateSync Initiate Synchronization 0=Inactive, 1=Active
4 1 Bool 0 Clear_kW_Hrs (Rev. 2.x)
Set_kW_Hrs (Rev. 3.x or later)
Set/Clear kW Hours 0=De-assert,
1=Assert
Bool 1 Clear_kVAR_Hrs (Rev. 2.x)
Set_kVAR_Hrs (Rev. 3.x or later)
Set/Clear kVAR Hours
Bool 2 Clear_kVA_Hrs (Rev. 2.x)
Set_kVA_Hrs (Rev. 3.x or later)
Set/Clear kVA Hours
Bool 3 Spare7
Bool 4 Droop_CCC_Select Droop/Cross Current
Compensation Select
0=Droop, 1=CCC
Bool 5 V_DroopEn Voltage Droop Enable 0=Disabled,
1=Enabled
Bool 6 Spare8
Bool 7 SoftwareExcEn Software Excitation Enable 0=Disabled,
1=Enabled
5 1 Bool 0 Spare9 - -
Bool 1 Spare10
Bool 2 Spare11
Bool 3 Spare12
Bool 4 kVAR_LS_BridgeEn kVAR Load Share Bridge Enable 0=Disabled,
1=Enabled
Bool 5 kVAR_LS_En kVAR Load Share Enable
Bool 6 kW_LS_BridgeEn kW Load Share Bridge Enable
Bool 7 kW_LS_En kW Load Share Enable
6 1 Bool 0…7 Spare13_20 - -
7 1 Bool 0…7 Spare21_28 - -
8 4 Real N/A AVRSetpt Automatic Voltage Regulator
Setpoint
Volts 85…30,000
12 4 Real N/A FCRSetpt Field Current Regulator Setpoint Adc 0…15
16 4 Real N/A PFSetpt Power Factor Setpoint PF -0.5…0.5
20 4 Real N/A VARSetpt VAR Setpoint VARS -1E+07…1E+07
24 4 Real N/A kWLSOutV kW Load Share Output Voltage Volts
28 4 Real N/A kWAnalogTargetPUValue kW Analog Target Value Per Unit -
Table 10 - Output (scheduled write) Data Table, Assembly Instance 1
Byte Size
in
Bytes
Type Bits Tag Name Description Units Range