Manual

142 Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 6 CGCM Unit Software Interface
Data Table
Although the Unscheduled Write tag is contained in the Configuration tag in the
Logix controller tags, the Unscheduled Write must be read back from the
CGCM unit independently.
Message size depends on the unit’s firmware revision. 64 (FRN 2.x) or 76 (FRN
3.x or later) byte Message size from CNET to CGCM (Written to the CGCM
unit).
Table 15 - Unscheduled Write Data Table, Assembly Instance 6
Byte Size in
Bytes
Type Tag Name Description Units Range Error
Code
0 4 Real LineDropComp Line Drop Compensation % 0…10 1
4 4 Real AVR_FCR_Kp Automatic Voltage Regulator/Field Current
Regulator Proportional Gain
-01000 2
8 4 Real AVR_FCR_Ki Automatic Voltage Regulator/Field Current
Regulator Integral Gain
-01000 3
12 4 Real AVR_FCR_Kd Automatic Voltage Regulator/Field Current
Regulator Derivative Gain
-01000 4
16 4 Real AVR_FCR_Td Automatic Voltage Regulator/Field Current
Regulator Derivative Time Constant
-01000 5
20 4 Real AVR_Kg Automatic Voltage Regulator Overall Gain - 0…1000 6
24 4 Real FCR_Kg Field Current Regulator Overall Gain - 0…1000 7
28 4 Real PF_Kg Power Factor Overall Gain - 0…1000 8
32 4 Real PF_Ki Power Factor Integral Gain - 0…1000 9
36 4 Real VAR_Kg VAR Overall Gain - 0…1000 10
40 4 Real VAR_Ki VAR Integral Gain - 0…1000 11
44 4 Real OEL_Kg Over-excitation Limiting Overall Gain - 0…1000 12
48 4 Real OEL_Ki Over-excitation Limiting Integral Gain - 0…1000 13
52 4 Real UEL_Kg Under-excitation Limiting Overall Gain - 0…1000 14
56 4 Real UEL_Ki Under-excitation Limiting Integral Gain - 0…1000 15
60 4 Real V_Match_Gain Voltage Match Gain - 0…1000 16
64 4 Real kWHoursPreset kW Hours Preset
-1 x 10
12
…1 x 10
12
17
68 4 Real kVARHoursPreset kVAR Hours Preset
-1 x 10
12
…1 x 10
12
18
72 4 Real kVAHoursPreset kVA Hours Preset
0…1 x 10
12
19
TIP
The last three elements are present only in the CGCM unit host firmware
revision 3.x or later.