144 Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 6 CGCM Unit Software Interface
The Set Attributes Single service for instance 6 of the Assembly Object can access
the following information.
Configuration Checking
When configuration data is received, the CGCM unit verifies that individual
parameters are within the minimum and maximum values indicated in the table
below (for example, perform range checking). If an out-of-range parameter is
detected, the CGCM unit enters a configuration fault mode and ignores all data
in the configuration write. The Connection tab in the module configuration
dialog box in RSLogix 5000 software displays an error code corresponding to the
first offending configuration parameter. The CGCM unit does not perform any
application checking (for example, is a value suitable for the particular
application) or dependency checking (for example, is a value reasonable based on
other values entered).
Data Table
Table 17 - Set Attributes Single (service code 0x10)
Name Attribute ID Data Type Value
Data 3 UINT See
Unscheduled Configuration
Read/Write Data Table, Assembly
Instance 4
IMPORTANT
Use of this service is not recommended. See the note above.
Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4
Byte Size in
Bytes
Type Bits Tag Name Description Units Range Error Code
0 1 SINT N/A Space Reserved for Logix controller Revision Configuration Number
1 3 SINT N/A Pad Bytes Reserved for Logix controller Usage
4 1 Bool 0 RevVARFltOutEn Reverse VAR Fault Output
Enable
- 0=Disabled,
1=Enabled
Bool 1 RevPwrFltOutEn Reverse Power Fault Output
Enable
Bool 2 OvrExcFltOutEn Over-excitation Fault Output
Enable
Bool 3 Ovr_I_FltOutEn Over-current Fault Output
Enable
Bool 4 Undr_V_FltOutEn Under-voltage Fault Output
Enable
Bool 5 OvrVFltOutEn Over-voltage Fault Output
Enable
Bool 6 UndrFreqFltOutEn Under-frequency Fault
Output Enable
Bool 7 OvrFreqFltOutEn Over-frequency Fault Output
Enable