Rockwell Automation Publication 1407-UM001G-EN-P - April 2013 197
Appendix
D
Specifications
The CGCM unit’s electrical and physical characteristics are listed in the
following tables.
Control Power
Excitation Power
Supply Burden
18…32V DC (24V DC nom)
(The device is to be powered by a
24V Nominal Battery or 24V DC Power Supply
with ATEX certification.)
30 W
AC ripple, max 50%, 50…120 Hz
Source Phases Wiring Configuration Voltage Frequency VA (max)
PMG
(1)
Single-phase PMG-A and PMG-C Min 56 Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
PMG 3-phase Floating wye Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE
(2)
Single-phase PMG-A and PMG-C Min 56Vrms
Max 300 Vrms
Min 50 Hz
Max 342 Hz
3070
SE 3-phase Floating wye Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE 3-phase Grounded wye
(grounded neutral)
Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE 3-phase Floating delta Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
SE 3-phase Open delta, floating Min 56Vrms L-L
Max 300 Vrms L-L
Min 50 Hz
Max 342 Hz
3070
(1) PMG = Permanent Magnet Generator.
(2) SE = Separately Excited.