200 Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Appendix D Specifications
Remote Excitation Enable Input
Open Collector Outputs (fault relay and redundancy relay)
Field Output
Attribute 1407-CGCM
Voltage rating 24V DC nom
Input impedance 5.6K
Logical high voltage, min 18V DC
Logical low voltage, max 5V DC
Attribute 1407-CGCM
Voltage rating 24V DC nom
Voltage range 18…30V DC
Rated current, max 500 mA
Attribute 1407-CGCM
Continuous voltage
32, 63, 125V DC
(1)
(1) Available output voltage is dependent on magnitude of excitation power input voltage.
Continuous current 15 A DC
10-second forcing voltage 50, 100, or 200V DC
10-second forcing current 30 A DC
Field resistance, min 32V DC
63V DC
125V DC
2.13
4.2
8.3