Rockwell Automation Publication 1407-UM001G-EN-P - April 2013 201
Specifications Appendix D
Regulation
The following modes are used to regulate the CGCM unit.
AVR Operating Mode
Accuracy: ±0.25% over the load range at rated power factor and constant
generator frequency.
Steady State Stability: ±0.1% at constant load and generator frequency.
Temperature Drift: The maximum error due to temperature drift will be
0.005% of full scale per degrees Celsius for voltage and current
measurements and 0.010% of full scale per degree Celsius for watt and
VAR measurements.
V/Hz Characteristic: Slope from 0 to 3PU is adjustable in 0.1PU
increments. Two knees and two slopes are available.
Response Time: < 1 cycle.
FCR Operating Mode
Accuracy: ±1% of rated current.
VAR Operating Mode
Accuracy: ±0.4% of the nominal VA rating at the rated frequency.
Power Factor Mode
Accuracy: ±0.02% of the PF setpoint for the real power between
10…100% at the rated frequency.
Parallel Compensation
Loss of Excitation
Attribute 1407-CGCM
Modes Reactive Droop
Reactive Differential (cross-current)
Droop adjust range 0…30%
Accuracy ±0.3% of rated cross current input current
Line-drop compensation range 0…10% of rated voltage in 0.1% increments
Attribute Range Increment
Pickup 0.1…15 A 0.1 A
Time delay 0.1…9.9 s 0.1 s