Manual

202 Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Appendix D Specifications
Over-excitation Voltage Protection
Over-current Protection
Under-voltage Protection
Over-voltage Protection
Loss of Sensing Protection
Attribute Range Increment
Pickup 1…200V DC 1V DC
Time delay 0.1…30 s 0.1 s
Attribute Range Increment Accuracy
Pickup 10…320% of rated
generator current
1% ±2% rated current
Time delay Characteristic inverse
per ANSI C50.13
configurable
0.1 s
Attribute Range Increment Accuracy
Pickup 60…100% of rated
generator voltage
1% ±2% rated voltage
Time delay 0.1…300 s ±0.1 s
Attribute Range Increment Accuracy
Pickup 100…140% of rated
generator voltage
1% ±2% rated voltage
Time delay 0.1…300 s ±0.1 s
Attribute 1407-CGCM
Pickup See text description in Operation section of the manual for this item
Time delay 0.1 s for normal operation, 1 s during soft start