Manual

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013 29
Installation Chapter 2
Figure 16 - Voltage and Current Connection for Single Phase Bus and Single-phase
Generator System
L1 L2 L3
CB
Fuse
Fuse
TB 6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
G
AC
B
TB3
I1 (+) 5 A
I1 (-)
ID (+ ) 5 A
I3 (+) 5 A
I2 (+) 5 A
I2 (-)
I3 (-)
ID ( -)
I1 (+) 1 A
I2 (+) 1 A
I3 (+) 1 A
ID (+ ) 1 A
To optional cross-current
reactive compensation loop.
Cross-current CT input
not required for parallel
droop operation.
Customer Supplied CT
Shorting Switch or Test
Block