98 Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Chapter 4 CGCM Unit Configuration
Related Parameters
• GenVT_Config
• BusVT_Config
• GenRated_V
Load Share Tab
The Load Share tab is used to configure the unit’s parameters related to the real
power load sharing function of the unit.
• Full Scale Voltage - Sets the load share output voltage when the generator
is producing rated real power. The tag LS_FS_V in the configuration table
stores this value, expressed in volts.
• Limit - Sets the maximum per unit load share error reported to the host
controller. The tag LSLimit in the configuration table stores this value,
expressed in per unit power.
• Rate - Sets the maximum change in the load share error per CGCM unit
update cycle. The tag LSRate in the configuration table stores this value,
expressed in seconds per rated watts.
Related Parameters
• GenRated_W