PowerMonitor 1000 Data Tables Appendix A
9 30910 Flash Memory 0…511 0 indicates normal operation. Status bits are
Bit 0 = Overall status
Bit 1 = Boot code checksum
Bit 2 = Application code checksum
Bit 3 = Calibration data CRC
Bit 4 = No calibration data
Bit 5 = Wrong application FRN
Bit 6 = Invalid model type
Bit 7 = WIN mismatch
Bit 8 = missing upgrade block
10 30911 SRAM 0…1 0 indicates normal operation.
Bit 0 = Read/write test
11 30912 NVRAM 0…1 0 indicates normal operation.
Bit 0 = Read/write test
12 30913 SPI Interface 0…1 0 indicates normal operation.
Bit 0 = SPI device not responding
13 30914 Real Time Clock 0…3 0 indicates normal operation.
Bit 0 = RTC status
Bit 1 = Time Zone Set Failed
14 30915 Watchdog Timer 0…1 0 indicates normal operation.
Bit 0 = Watchdog time out
15 30916 Metering 0…1 0 indicates normal operation.
Bit 0 = Metering status
16 30917 LCD Interface 0…1 0 indicates normal operation.
Bit 0 = LCD Interface status
17 30918 Serial Communications 0…1 0 indicates normal operation.
Bit 0 = Serial Interface status
18 30919 Ethernet Communications 0…511 0 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status
19 30920 Input Over Range 0…3 0 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range
20 30921 Phase Loss Detection 0…7 0 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C
21 30922 Configuration Locked 0…1 Reports 1 if configuration lock is applied.
22 30923 Password Accepted 0…1 1 indicates the password is verified and active
23 30924 Error Recorded 0 Is incremented by 1 when an internal error happens
24 30925 Troubleshooting Times
Remaining
0…30 Remaining times for troubleshooting mode.
Table 43 - Unit Run Status Results
Element
No.
Modbus
Address
Element Name Range Description