Instruction Manual
102 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 44 - Min/Max Log Results Parameters
CSP File No. F29
CIP Instance 22
No. of Elements 11
No. of Words 22
Data Type Float
Data Access Read
Table 45 - Min/Max Log Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 31001-2 Parameter Being
Returned
1…35 •• •Indicates the Parameter Number (See Min/
Max Parameter List).
1 31003-4 MIN Value +/-
0.000…9,999,
999
•• •The minimum value recorded for parameter
being returned since the last clear
command.
2 31005-6 MAX Value +/-
0.000…9,999,
999
•• •The maximum value recorded for
parameter being returned since the last
clear command.
3 31007-8 Timestamp Year of MIN •• •The year when the MIN value was
recorded.
4 31009-10 Timestamp Month/Day
of MIN
•• •The month and day when the MIN value
was recorded.
5 31011-12 Timestamp Hour/Minute
of MIN
•• •The hour and minute when the MIN value
was recorded.
6 31013-14 Timestamp Seconds/
Hundredths of MIN
•• •The seconds and hundredths when the
MIN value was recorded.
7 31015-16 Timestamp Year of MAX •• •The year when the MAX value was
recorded.
8 31017-18 Timestamp Month/Day
of MAX
•• •The month and day when the MAX value
was recorded.
9 31019-20 Timestamp Hour/Minute
of MAX
•• •The hour and minute when the MAX value
was recorded.
10 31021-22 Timestamp Seconds/
Hundredths of MAX
•• •The seconds and hundredths when the
MAX value was recorded.