Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 105
PowerMonitor 1000 Data Tables Appendix A
9 31119-20 Peak Demand kVA 0.000…
9,999,999
••The largest magnitude demand for kVA that
occurred over all of the demand intervals
since the last clear command or auto-clear
day.
10 31121-22 Average Demand
kVA
0.000…
9,999,999
••A running average of demand for kVA from
the end of each demand period since the
last clear command or auto-clear day.
11 31123-24 Load Factor kVA 0…100% ••Average Demand kVA / Peak Demand kVA.
This is a demand management metric that
indicates how ‘spiky’ (or ‘level’) a load is
over a period of time (usually 1 month). A
value approaching 100% indicates a
constant load.
12 31125-26 Reserved 0 • • Reserved for Future Use
13 31127-28 Reserved 0 • • Reserved for Future Use
Table 48 - Load Factor Log Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description