Instruction Manual
106 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 49 - Time of Use Log Results - Real Energy and Demand Parameters
CSP File No. F31
CIP Instance 24
No. of Elements 12
No. of Words 24
Data Type Float
Data Access Read
Table 50 - Time of Use Log Results - Real Energy and Demand
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 31201-2 Record Number 1…13 •••The record number of the log. Record 0 is
always the current record before being
logged.
1 31203-4 Time Stamp Start
Date (yy/mm/dd)
- •••The Date this record was started.
2 31205-6 Time Stamp End
Date (yy/mm/dd)
- •••The Date this record was ended.
3 31207-8 Off Peak GWh Net +/- 0…
9,999,999
•••Net Off Peak giga watt hours
4 31209-10 Off Peak kWh Net +/- 0.000…
999,999
•••Net Off Peak kilo watt hours
5 31211-12 Off Peak kW
Demand
+/- 0.000…
9,999,999
•••Off Peak Demand for kilo watts
6 31213-14 Mid Peak GWh Net +/- 0…
9,999,999
•••Net Mid Peak giga watt hours
7 31215-16 Mid Peak kWh Net +/- 0.000…
999,999
•••Net Mid Peak kilowatt hours
8 31217-18 Mid Peak kW
Demand
+/- 0.000…
9,999,999
•••Mid Peak Demand for kilo watts
9 31219-20 On Peak GWh Net +/- 0.000…
9,999,999
•••Net On Peak giga watt hours
10 31221-22 On Peak kWh Net +/- 0…
999,999
•••Net On Peak kilo watt hours
11 31223-24 On Peak kW
Demand
+/- 0.000…
9,999,999
••On Peak Demand for kilo watts