PowerMonitor 1000 Data Tables Appendix A
Table 51 - Time of Use Log Results - Reactive Energy and Demand Parameters
CSP File No. F32
CIP Instance 25
No. of Elements 12
No. of Words 24
Data Type Float
Data Access Read
Table 52 - Time of Use Log Results - Reactive Energy and Demand
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 31301-2 Record Number 1…13 •••The record number of the log. Record 0 is always
the current record before being logged.
1 31303-4 Time Stamp Start
Date (yy/mm/dd)
- •••The Date this record was started.
2 31305-6 Time Stamp End
Date (yy/mm/dd)
- •••The Date this record was ended.
3 31307-8 Off Peak GVARH
Net
+/- 0…
9,999,999
•••Net Off peak giga VAR hours
4 31309-10 Off Peak kVARh
Net
+/- 0.000…
999,999
•••Net Off Peak kilo VAR hours
5 31311-12 Off Peak kVAR
Demand
+/- 0.000…
9,999,999
•••Off Peak Demand for kilo VAR
6 31313-14 Mid Peak GVARH
Net
+/- 0…
9,999,999
•••Net Mid Peak giga VAR hours
7 31315-16 Mid Peak kVARh
Net
+/- 0.000…
999,999
•••Net Mid Peak kilo VAR hours
8 31317-18 Mid Peak kVAR
Demand
+/- 0.000…
9,999,999
•••Mid Peak Demand for kilo VAR
9 31319-20 On Peak GVARH
Net
+/- 0.000…
9,999,999
•••Net On Peak giga VAR hours
10 31321-22 On Peak kVARh
Net
+/- 0…
999,999
•••Net On Peak kilo VAR hours
11 31323-24 On Peak kVAR
Demand
+/- 0.000…
9,999,999
••On Peak Demand for kilo VAR