Instruction Manual

108 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 53 - Time of Use Log Results - Apparent Energy and Demand Parameters
CSP File No. F33
CIP Instance 26
No. of Elements 12
No. of Words 24
Data Type Float
Data Access Read
Table 54 - Time of Use Log Results - Apparent Energy and Demand
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 31401-2 Record Number 1…13 •••The record number of the log. Record 0 is always
the current record before being logged.
1 31403-4 Time Stamp Start
Date (yy/mm/dd)
- •••The Date this record was started.
2 31405-6 Time Stamp End
Date (yy/mm/dd)
- •••The Date this record was ended.
3 31407-8 Off Peak GVAh Net +/- 0…
9,999,999
•••Net Off peak giga VA hours
4 31409-10 Off Peak kVAh Net +/- 0.000…
999,999
•••Net Off Peak kilo VA hours
5 31411-12 Off Peak kVA
Demand
+/- 0.000…
9,999,999
•••Off Peak Demand for kilo VA
6 31413-14 Mid Peak GVAh
Net
+/- 0…
9,999,999
•••Net Mid Peak giga VA hours
7 31415-16 Mid Peak kVAh Net +/- 0.000…
999,999
•••Net Mid Peak kilo VA hours
8 31417-18 Mid Peak kVA
Demand
+/- 0.000…
9,999,999
•••Mid Peak Demand for kilo VA
9 31419-20 On Peak GVAh Net +/- 0.000…
9,999,999
•••Net On Peak giga VA hours
10 31421-22 On Peak kVAh Net +/- 0…
999,999
•••Net On Peak kilo VA hours
11 31423-24 On Peak kVA
Demand
+/- 0.000…
9,999,999
••On Peak Demand for kilo VA