Feature Description
1. Ethernet network port -
standard RJ-45 jack with
status indicators
Ethernet network port hardware is included on all models. The port functions only on units ordered with or upgraded to
the Ethernet network. The following protocols and functions are supported.
EtherNet/IP
Modbus TCP
HTML Web page for configuration and data access
LNK indicator
Solid GREEN: IP link established
Off: no link established
ACT indicator
Flashing YELLOW: data present on Ethernet port
Off: no data activity present
2. Serial port - three-pin RS-
485 connector
All models include RS-485 serial communication that support the following protocols and functions.
DF1 half-duplex slave
DF1 full-duplex
Modbus RTU slave
Configuration using the HyperTerminal communication tool
DH-485
3. Serial port status indicators TX indicator flashes YELLOW when data is being transmitted
RX indicator flashes YELLOW when data is being received
4. LCD Unit configuration
Data display
5. Module and network status
indicators
Module indicator
GREEN: Normal operation
Alternating RED/GREEN: Performing self-test
RED (solid or blinking): Initial power-up or failed self-test
Network indicator
GREEN: Ethernet connection established
Blinking GREEN: Ethernet port looking for a connection
RED: Duplicate IP address detected
6. LCD interface buttons Unit configuration