Instruction Manual
110 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 57 - Single-element Password Write Parameters
CSP File No. N35
CIP Instance 28
Applies to All models
No. of Elements 1
No. of Words 1
Data Type Integer
Data Access Write
Table 58 - Single-element Password Write
Element
No.
Modbus
Address
Element
Name
Range Description
0 40901 Password 0…9999 A write of this table allows any configuration parameter to be written as a single element or
poke. The password stays active for 30 minutes and resets to another 30 minutes when a
single element is configured.