Instruction Manual

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 111
PowerMonitor 1000 Data Tables Appendix A
Table 59 - User-configurable Table Setup Parameters
CSP File No. N44
CIP Instance 29
Applies to EM3 only
No. of Elements 17
No. of Words 17
Data Type Integer
Data Access Read/Write
Table 60 - User-configured Table Setup
Element
No.
Modbus
Address
Element Name Default Value Range Description
0 41001 Password 0 0…9999 Required for configuration,
returns -1.
1 41002 Selection for Parameter #1 29 (L1 Current) 0…110
2 41003 Selection for Parameter #2 30 (L2 Current)
3 41004 Selection for Parameter #3 31 (L3 Current)
4 41005 Selection for Parameter #4 37 (L1-L2 Voltage)
5 41006 Selection for Parameter #5 38 (L2-L3 Voltage)
6 41007 Selection for Parameter #6 39 (L3-L1 Voltage)
7 41008 Selection for Parameter #7 41 (Frequency)
8 41009 Selection for Parameter #8 52 (Total Real Power)
9 41010 Selection for Parameter #9 56 (Total Reactive Power)
10 41011 Selection for Parameter #10 60 (Total Apparent Power)
11 41012 Selection for Parameter #11 48 (3 Phase True Power Factor)
12 41013 Selection for Parameter #12 70 (Real Energy Net (kWh))
13 41014 Selection for Parameter #13 62 (Status 1 Count x1)
14 41015 Selection for Parameter #14 64 (Status 2 Count x1)
15 41016 Selection for Parameter #15 79 (Real Power Demand)
16 41017 Selection for Parameter #16 8 (Status Input States)