Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 123
SCADA Applications Appendix B
Reading the User Configured Table as Connected Instance 1
The following example illustrates the steps required to set up an I/O connection
between a Logix controller and the user configured Instance 1. The example uses
a CompactLogix controller and RSLogix 5000 software.
Follow these steps to configure the connection.
1. Open an offline project in RSLogix 5000 software.
2. Open the Ethernet network interface and select the Ethernet network.
3. Add a new module and choose Generic Ethernet Module from the
Communication group.
4. Configure the properties of the new module and click OK.
5. On the connection tab, enter the desired Requested Packet Interval (RPI).
Parameter Choice
Name Your choice of name
Comm Format Input Data - REAL
IP Address The IP address of your power monitor
Input Assembly Instance 1; Size 16 (32-bit)
Output Assembly Instance 2
Configuration Assembly Instance 3; Size 0
Open Module Properties Leave checked