PowerMonitor 1000 Unit Features
This section describes in detail the functions of the power monitor. Each
function includes information on set-up menus and parameters used to control its
operation.
Analog Input Setup
This feature applies to all models.
Setup
The power monitor calculates metering results based on scaled voltage and current inputs. Setting
up the analog inputs is necessary to obtain accurate, properly scaled metering results.
Related Functions
• Wiring diagnostics
• Configuration lock
Parameter Description Range Default User
Setting
Voltage mode Should match the external electrical system and how it is
wired to the PowerMonitor voltage and current input
terminals. Refer to the wiring diagrams.
0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo, simulated results
5 = 1PT1CT-LL
6 = 1PT1CT-LN
0…4 2
PT primary The primary value of the PT ratio (Pri:Sec) indicating the
nominal voltage present at the high-end of the transformer.
For direct connect, set the PT ratio to any valid 1:1 ratio (for
example, 480:480).
1.00… 50,000 480
PT secondary The secondary value of the PT ratio (Pri:Sec) indicating the
nominal voltage present at the low-end of the transformer.
1…600 480
CT primary The primary value of the CT ratio (Pri:5) indicating the nominal
current present at the high-end of the transformer. The
nominal CT rated current is 5 A.
5…50,000 5
System PF setting Select range corresponding to expected power factor. 0 = Lead (-97…89)
1 = High (-85…98)
2 = Low (-52…-95)
2 = Low