Chapter 2 PowerMonitor 1000 Unit Features
Results
Power metering results may be viewed using the following methods:
• Web inter fac e
• LCD screen
• Communication
• HyperTerminal communication tool
Related Functions
• Metering result averaging
• Configuration lock
Voltage, Current, and
Frequency Metering
This function applies to catalog numbers 1408-TR1, 1408-TR2, and 1408-EM3.
Metered Parameters
The power monitor calculates and returns voltage, current, and frequency
measurements including these:
• L1, L2, L3, and Average Current, A
• L1-N, L2-N, L3-N, and Average L-N Voltage, V
• L1-L2, L2-L3, L3-L1, and Average L-L Voltage, V
• Frequency
• Percent Current Unbalance
• Percent Voltage Unbalance
Line-to-neutral voltage results are not provided for Delta and Open Delta wiring
modes.
Voltage and current unbalance are calculated according to the following formula.
Setup
Only basic analog-input setup is required for power metering.
Maximum Deviation from Average 100
Average
----------------------------------------------------------------------------------------------------------