Instruction Manual

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 43
PowerMonitor 1000 Unit Features Chapter 2
Status Log
The Status log records the date and time of changes made to the device and of
external events. The status log consists of 50 records and operates in a circular or
FIFO fashion. The status log may not be cleared.
This function applies to all models.
Logged Events
Configuration changed
Clock set
Relay output forced on or off
Status input activated or deactivated (may be disabled)
Status input counter 1 or 2 rollover or set
Missed external sync pulse
Energy register rollover or set
Device power-up or power-down
Self-test status
Results
Status log records can be accessed only via communication.
Related Functions
Log status input changes
I/O Functions
The I/O functions include Relay KYZ Output, Status Inputs, and Configuration
Lock Input.
Relay KYZ Output
The KYZ output is a solid-state relay designed for low-power, long-life signaling
operation. Its typical use is to provide a pulse output proportional to energy
consumption to an external totalizer.
This function applies to catalog numbers 1408-EM1, 1408-EM2, and 1408-EM3
for energy pulse.
This function applies to all models for forced operation.