Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 57
Explicit Messaging Chapter 5
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message Configuration window.
Parameter Choice
Message Type Choose message type CIP Generic.
Service Type Read: Select service type Get Attribute Single
Write: Select service type Set Attribute Single
Instance Refer to Appendix
A for the CIP Instance of the data table you are requesting to
read. In this example, the power monitor’s Voltage, Amp, and Frequency data
table is instance 14.
Class 4
Attribute 3
Destination Get Attribute Single - This is the controller tag in which to store the data being
read.
Source Element Set Attribute Single - Refer to Appendix
A for the address of the specific data
table address you’re writing to.
Source Length Set Attribute Single - This is the number of elements of the source element, to
be written to the power monitor.