Instruction Manual

70 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 4 - Analog Input Configuration Parameters
CSP File No. F10
CIP Instance 3
Applies to All models
No. of Elements 7
No. of Words 14
Data Type Float
Data Access Read/Write
Table 5 - Analog Input Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range Description
0 40001-2 Password 0 0…9999 When writing the complete table this parameter allows the input
data to be accepted. When writing a single parameter the separate
password table should be used. Returns -1 on a read.
1 40003-4 Voltage Mode 2 0…4 Should match the external electrical system and how it is wired to
the PowerMonitor’s voltage and current input terminals. Refer to
the installation manual wiring diagrams.
0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo
2 40005-6 PT Primary 480 1.00…
50,000
The first value of the PT ratio (xxx:xxx) indicating the nominal
voltage present at the high-end of the transformer. If no transformer
is used (for direct connect of up to 347V L-N or 600V L-L), set the PT
ratio to any valid 1:1 ratio (for example 480:480).
3 40007-8 PT Secondary 480 1.00…
600.00
The second value of the PT ratio (xxx:xxx) indicating the nominal
voltage present at the low-end of the transformer.
4 40009-10 CT Primary 5 5.00…
50,000
The first value of the CT ratio (xxx:5) indicating the nominal current
present at the high-end (primary side) of the transformer.
Example: PRI = 1000. Setting = 1000:5.
5 A is the nominal secondary current of the CT.
5 40011-12 System PF Setting 2 0…2 0 = Leading -97…89
1 = High -85…98
2 = Low -52…-95
6 40013-14 Reserved 0 0 Reserved for future use.