Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 71
PowerMonitor 1000 Data Tables Appendix A
Table 6 - Advanced Configuration Parameters
CSP File No. F11
CIP Instance 4
No. of Elements 22
No. of Words 44
Data Type Float
Data Access Read/Write
Table 7 - Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40101-2 Password 0 0…9999 •••••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single parameter the
separate password table should be used.
Returns -1 on a read.
1 40103-4 New Password 0 0…9999 •••••This becomes the new password when the
proper the configuration password entry has
been made and this parameter is greater than (-
1).
2 40105-5 Metering
Result
Averaging
10…1•••••The metering results for volts, amps, power and
frequency is averaged over 8 cycles of data to
provide a steady output reading.
0 = Off
1 = On
3 40107-8 Log Status
Input Changes
00…1•••••0 = Disable recording of status input changes
into the status log.
1 = Enable recording of status input changes
into the status log.
4 40109-10 Use Daylight
Savings
Correction
00…1•••••0 = Disable Daylight Savings
1 = Enable Daylight Savings
5 40111-12 Daylight
Savings
Month/Week/
Day Start
030201
March, 2nd,
Sunday
10101…
120507
•••••This is the day that the power monitor will add
an hour to the time. This feature also looks at
Ethernet SNTP offset and corrects for Daylight
Savings.
Example: 040107 = April/1st week/Sunday
Month Settings:
01 = January…12 = December
Week Settings:
01 = 1st week…05 = Last Week
Day of the Week Settings:
01 = Sunday…07 = Saturday
6 40113-14 Hour of Day
Start
2 0…23 •••••The hour of day the daylight savings
adjustment should be made to add an hour.