Instruction Manual

74 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 8 - Serial RS-485 Port Configuration Parameters
CSP File No. N12
CIP Instance 5
Applies to All models
No. of Elements 9
No. of Words 9
Data Type Integer
Data Access Read/Write
Table 9 - Serial RS-485 Port Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range Description
0 40201 Password 0 0…9999 When writing the complete table this parameter allows the input data to
be accepted. When writing a single parameter the separate password
table should be used. Returns -1 on a read.
1 40202 Protocol Setting 1 0…3 The protocol selection for communication.
0 = DF1 Half Duplex Slave
1 = DF1 Full Duplex
2 = Modbus RTU Slave
3 = Auto Sense
4 = DH485
2 40203 Serial Delay 2
(10 ms)
1…15 The setting times 5 = milliseconds that the unit waits before responding to
a communication request. Useful for consistent communication and slow
devices.
3 40204 Baud Rate 5 0…6 The serial communication baud rate.
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38,400
6 = 57,600
4 40205 DF1, DH485,
Modbus Address
Device
ID,
31 for
DH485
1…247
(DF1,
Modbus)
0…31
(DH485)
During production the Device ID is printed on the nameplate. This ID then
becomes the default address for DF1 and Modbus.
5 40206 Data Format 0 0…2
(2 for
DH485)
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
6 40207 Inter Character
Timeout
00
6553
Specifies the minimum delay between characters that indicates the end of
a message packet for Modbus protocol. 0 = 3.5 character times in default.
The unit is ms.
8 40208 Maximum Node
Address
3 1…31 Specifies the maximum node address on a DH485 network.
9 40209 Reserved 0 0 Reserved for future use.