Instruction Manual

76 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
13 40314 SNTP Mode Select 0 0…2 •••••This mode selects the mode of the SNTP
function or to disable the SNTP function.
0 = Disable
1 = Unicast - The SNTP address points to a
unicast server.
2 = Anycast Mode - The SNTP address is a
broadcast address of an anycast group.
14 40315 SNTP Update Interval 300 1…32766 •••••Indicates how often the time is updated from
the SNTP Server. The unit is minute.
15 40316 Time Zone Select 7 0…32 •••••The time zone table has detailed time zone
information.
16 40317 Time Server IP
Address Byte a
00255•••••The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
17 40318 Time Server IP
Address Byte b
00255•••••The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
18 40319 Time Server IP
Address Byte c
00255•••••The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
19 40320 Time Server IP
Address Byte d
00255•••••The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
20 40321 Demand Broadcast
Master Select
001 ••When configured as a Master the power
monitor broadcasts an end of demand
interval broadcast to the UDP port number
configured.
0 = Slave
1 = Master control
21 40322 Broadcast Port
Number
300 300…400 ••When configured as a Master and External
Demand Source or Ethernet Demand
Broadcast the port number is the listening or
broadcast port for the UDP message.
22 40323 Reserved 0 0 Reserved for future use.
Table 11 - Ethernet Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description