Appendix A PowerMonitor 1000 Data Tables
Table 15 - Log Configuration Parameters
CSP File No. N15
CIP Instance 8
No. of Elements 12
No. of Words 12
Data Type Integer
Data Access Read/Write
Table 16 - Log Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40501 Password 0 0…
9999
•••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single parameter
the separate password table should be used.
Returns -1 on a read.
1 40502 Energy Log
Interval
15 min -1…60 •••Selects how often a record is logged
(minutes). A value of 0 disables periodic
logging of records. A value of –1 causes
logging of records to be synchronized to the
end of the demand interval.
2 40503 Energy Log Mode 1 0…1 •••This parameter set the action of the log once
is has filled to capacity. Setting the option to
0 allows the log to fill but stops at the end.
Option 1 lets the log fill and then oldest
records are deleted and replaced with new
records.
0 = Fill and Stop
1 = Overwrite, When the log is filled new
records replace the oldest records.
3 40504 Time of Use Log
Auto Log Setting
31 0…31 •••Automatically stores the current record for
the month replacing the oldest record if the
log is full. The log holds 12 months plus the
current record.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st day of
each month.
2 = 2nd Day
3 = 3rd day
…
29…31 = Store and clear table at the last
day of the month.